Sensors and Systems for combustion technology

LT3-F for the failsafe Lamtec CO/O2 regulation (SIL2)

  • Display of O2 and COe measured values
  • Calibration of measurements
  • Up to 1200 °C flue gas temperatures
  • COe measurement not influenced by ingress air
Technical Data
Housing:Mounting house of sheet steel
Protection class:

IP54 with display

Dimensions (HxWxD):300 x 300 x 120 mm
Weight:Approx. 6 kg
Ambient temperature operation:-20 °C ... +60 °C
Ambient temperature transport and storage:-20 °C ... +70 °C
Power supply:120 VAC ... 230 VAC, 50 ... 60 Hz
Power consumption:

Typically 30 W

Maximum 69 W

Range of measuring:

O2: 0 ... 21 Vol. % (configurable)
COe: 0 ... 10.000 ppm (configurable)

Resolution:O2: 0,1 Vol. %
COe: 1 ppm
Analogue, digital Inputs/Outputs:See download area (technical data LT3-F)
Measuring probe:See selection criteria

Approvals:

 

EC type-examination certificate:

  • DIN EN 16340:2014-10
  • DIN EN 13611:2011-12
  • DIN EN 60730-1:2012-10


SIL 2 Confirmation:

  • DIN EN 61508 part 1-7
  • DIN EN 16340


EC-declaration of conformity:

  • 2009/142/EC (Gas Appliance Directive)
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
 
Purpose Selection criteria Download