Sensors and Systems for combustion technology

Flame Monitoring Device F130I

Flame Monitoring Device F130I
  • Suited for single burners at heating stations and process furnaces
  • Approved for permanent operation with ionisation
  • UV tubes and LDR sensors, approved for intermittent operation
  • Suited for fuels such as oil, gas, biomass, dust and process gases
  • Plug-in module for top hat rail assembly
  • Two-channel system with electronic self-monitoring
  • The F130I flame monitoring device is designed for installation in switch cabinets
  • LED-based status display
  • No modifications needed for country-specific mains frequencies

Power supply voltage:

230 VAC +10 % -15 %
120 VAC +10 % -20 %

Flame and signal contact:

floating

Mains frequency:

47 Hz … 63 Hz

Safety time "operation":

tVoff ≤ 1 s

Mode of operation:

continuous operation

Protection class:

IP20

Operating temperature:

-20 °C … +60 °C

Dimensions:

114 x 120 x 45 mm (TxHxB)

Weight:

0,5 kg

Approvals:

EC type-examination certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012
  • DIN EN 13611:2011
  • DIN EN 60730-2-5:2011
  • DIN EN 60730-1:2012
  • DIN EN 746-2:2011 for process burners

 

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

 

CE Declaration of Confomity

  • 2014/68/EU (Pressure Equipment Directive)
  • 2009/142/EC (Gas Appliance Directive)
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)

The F130I flame monitoring device is LAMTEC's new safety system, designed specially for monitoring ignition and main flames.The F130I flame monitoring device by LAMTEC provides operators of industrial firing systems and power plants with a reliable high-tech device for flame monitoring.

The F130I uses ionisation to monitor the flame. Optical flame sensors can also be connected to the device. The F130I flame monitoring device is particularly impressive when used for more demanding monitoring requirements, such as monitoring in firing systems with single burner flames. The ionisation-based F130I flame monitoring device has been approved for permanent operation.

The evaluation device may only be operated with the approved flame sensors. The F130I is not designed for the direct switch-off fuel valves. The subsequent signalprocessing must be carried out in the control system, which is adapted to suit the firing system in question.

Sensor type

F130I input

For fuel

Continuous operation

Wavelength range

UV tubes

UV

Gas / Oil

No

190 … 270 nm

LDR, visible

LDR

Oil

No

450 … 800 nm

LDR, visible

LDR

Oil

No

400 … 800 nm

Ionisation

ION

Gas

Yes

-