Sensors and Systems for combustion technology

Compact Flame Scanner F300K

  • 3 operating modes, can be externally preselected, switchable during operation
  • 14 graduated frequency ranges
  • Available as single or double sensor (IR/UV)
  • Can be completely operated without opening the device (degree of protection IP67 is retained, even during commissioning)
  • Menu-guided configuration and commissioning
    with Flame ON/OFF self-learning function
  • Alignment assistance by means of a logical graphical display of flame data
  • Operation via graphic User Interface with status display (optional)
  • SIL 3 according to DIN EN 61508 part 1-7
  • Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations
Technical Data
Supply voltage:24 VDC ± 20 % ≤ 3,5 W
Flame and fault contact:≤ 50 VDC, ≥ 6 VDC
≤ 0,5 A, ≥ 1,0 mA floating
Frequency range:10 / ... / 110 ... 210 Hz
7 levels in the standard version
Safety time "Operation":t ≤ 1 sec. (standard)
t ≤ 1, 2, 3, 4, 5 sec. (selectable via password)
Operating mode:Continuous operation
Degree of protection:IP67
NEMA 4X
Operation temperature:-40 °C ... + 85 °C
Dimensions (HxT):99x195,5 mm
Weight:1,05 kg (aluminium)
3,6 kg (stainless steel)
Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised
or stainless steel

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:

 


 


   

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

 

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

 

CE Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 module B+D)
  • 2009/142/EC (Gas Appliance Directive)

 

Available with Class I, Division 2, Group A, B, C, D, Hazardous Locations