Sensors and Systems for combustion technology

Compact Flame Scanner F200K Ex

  • Compact case with integrated flame sensor and dual amplifier for fail safe operation
  • Intensity adjust in multiple steps
  • Digital circuit design for flame evaluation
  • Status indication by LEDs
  • 24 VDC operating voltage
  • Two electronic channel system for fail safe operation and supervision
  • LED bar flame intensity indication and 4 (0) ... 20 mA analog output
  • SIL 3 following DIN EN 61508-2
Technical Data
Power supply: 24 VDC ± 20 %, ≤ 4,0 W 
Output contact:

≤ 42 VDC, ≥ 6 VAC/DC
≤ 0,5 A, ≥ 1,0 mA floating

Frequency range:10/20/30 ... 190 Hz
Safety time "operation":t ≤ 1 s (standard)
t ≤ 3 s (on request, at the factory)
Mode of operation:Continuous operation
Protection class:IP66
NEMA 4X
Operating temperature:-20 °C ... +60 °C 
Dimension:Total length: 216 mm
Diameter: 60/90 mm
Weight:2 kg
Material:

Corrosion-resistant aluminium EN AW 6082 (seawater 2*; atmospheric condition 1*), anodised

* Comparative evaluation from 1 (very good) to 6 (unsuitable)

Approvals:


EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298:2012-11

SIL 3 Confirmation

  • DIN EN 61508 Part 2

CE Declaration of Conformity

  • 2009/142/EC (Gas Appliance Directive)
  • 2014/68/EU (Pressure Equipment Directive)
Purpose Selection criteria Download