Sensors and Systems for combustion technology

Flame Monitoring Device F130I

  • Suited for single burners at heating stations and process furnaces
  • Approved for permanent operation with ionisation
  • UV tubes and LDR sensors, approved for intermittent operation
  • Suited for fuels such as oil, gas, biomass, dust and process gases
  • Plug-in module for top hat rail assembly
  • Two-channel system with electronic self-monitoring
  • The F130I flame monitoring device is designed for installation in switch cabinets
  • LED-based status display
  • No modifications needed for country-specific mains frequencies
Technical Data
Power supply voltage:

230 VAC +10 % -15 %
120 VAC +10 % -20 %

Flame and signal contact:Floating
Mains frequency:47 Hz … 63 Hz
Safety time "operation":tVoff ≤ 1 s
Mode of operation:Continuous operation
Protection class:IP20
Operating temperature:-20 °C … +60 °C
Dimensions:114 x 120 x 45 mm (TxHxB)
Weight:0,5 kg

Approvals:

EC type-examination certificate according to 2014/68/EU (Pressure Equipment Directive)
  • DIN EN 298:2012
  • DIN EN 13611:2011
  • DIN EN 60730-2-5:2011
  • DIN EN 60730-1:2012
  • DIN EN 746-2:2011 for process burners

 

SIL 3 Confirmation

  • DIN EN 61508 part 1-7

 

CE Declaration of Confomity

  • 2014/68/EU (Pressure Equipment Directive)
  • 2009/142/EC (Gas Appliance Directive)
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
 
Purpose Selection criteria Download