FFS07, FFS08
Flame Sensor & Flame Monitoring Device
Your advantages at a glance:
- Single burner systems
- Available for UV and IR
- Use in outdoor areas
- DIN EN 61508 Part 2 - SIL 3
- Suitable for Flame Monitoring Device F152 or Burner Controls CMS or ETAMATIC
The FFS07 / FFS08 flame sensors can be used for different areas. They are mainly used for
- Single and multi-fuel burners in heating plants
- Process cumbustion systems
- Hydrogen plants
- Natural gas, LFO
FFS07 and FFS08 are non-compact flame sensors, whereby the FFS07 is aligned axially in the direction of the flame and the FFS08 is aligned orthogonally to the flame axis.
Features:
The FFS07 and FFS08, together with the F152 flame monitor, rovide safety monitoring of burner flames without demanding selection tasks.
FFS07 is available for Ex-Zone I, Ex-Zone II and Safe Area.
FFS08 is available for Safe Area.
| Technical Data | |
| Approvals |
EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)
EC Type Examination Certificate according to 2016/426/EU (Gas Appliances Regulation)
SIL 3
CE Declaration of Conformity
USA and Canada
Ship certification
EX certicicate FFS07
|
| Non Compact | |||
| FFS07 | FFS08 | FFS30 | |
| Power supply voltage | F152 + 24 VDC | F152 + 24 VDC | F350 + 24 VDC |
| Operating mode | Continuous operation | Continuous operation | Continuous operation |
| Degree of protection | IP66 for Ex zone 1 | X | IP66 |
| IP67 for Ex zone 2 | No Ex zone, only as standard IP67 | IP67 | |
| Sensor type | UV, IR | UV, IR | UV, IR, UV/IR-1 Dual sensor |
| UV-1, UV-4, IR-1, IR-1 T | UV-1, UV-4, IR-1, IR-1 T, IR-1 T/S2 | UV-4, UV/IR-1, IR-2, IR-4 | |
| Operating temperature | -20 °C ... +65 °C (UV) | -20 °C ... +65 °C | -40 °C ... +85 °C |
| Operating temperature | -20 °C ... +60 °C (IR) | -20 °C ... +60 °C | |
| Ex zone 1 | II 2G Ex d IIC T6 Gb | II 2G Ex d IIC T6 Gb | |
| II 2D Ex tb IIIC T80 °C Db | X | II 2D Ex tb IIIC T80 °C Db | |
| Ex zone 2 | II 3G Ex nA IIC T5 (T6) Ge X | X | X |
| II 3D Ex tc IIIC T95 °C Dc X | X | X | |
| Display | X | X | Has to be connected with FB 30 |
| UL resp. Class 1 Div. 2 certified | UL 372 - UL listed | UL 372 - UL listed | UL / Cl 1 Div. 2 |
| Operation with Remote Software | X | X | Yes |
| Evaluation device | F152 | F152 | F350 |
| Safety Integrity Level (SIL) | F152 SIL 3 | F152 SIL 3 | F350 SIL 3 |
| Compact | ||
| F200K | F300K | |
| Power supply voltage | 24 VDC | 24 VDC |
| Operating mode | Continuous operation | Continuous operation |
| Degree of protection Ex zone 1 | IP66 | X |
| Degree of protection Ex zone 2 | IP66/67 | IP66/67 |
| Sensor type | UV, IR | UV, IR, UV/IR-1 dual sensor |
| UV-2, (Ex zone 1, Ex zone 2), UV-6 FO (Ex zone 2), IR-1 (Ex zone 1, Ex zone 2), IR-2 (no Ex zone) | UV-4, UV-4.6, UV-4.6 FO, UV/IR-1, IR-4, UV/IR-1 FO (as standard all in Ex zone 2) | |
| Operating temperature Ex zone 2 | -40 °C ... +75 °C (UV-2, UV-6 FO) | -40 °C ... +85 °C |
| -40 °C ... +60 °C (IR-1) | ||
| Operating temperature Ex zone 1 | -40 °C ... +65 °C (UV-2) | X |
| -40 °C ... +60 °C (IR-1) | ||
| Ex zone 1 | Ex II 2G, zone 1 // Ex II 2D- zone 21 | X |
| Ex db lic. T6 ... T5 Gb // Ex tb IIIC T80 °C, T95 °C Db | ||
| Ex zone 2 | Ex II 3G, zone 2 // Ex II 3D zone 22 | Ex nA nC ic IIC T5 (T6) Gc X |
| Ex nA nC IIC T6 ... T5 Gc X // Ex tc IIIC T85 °C Dc X | ||
| UL resp. Class 1 Div. 2 certified | UL certified/ Cl 1 Div.2 | UL certified/ UL + Cl 1 Div. 2 |
| Operation with Remote Software | X | Yes |
| Evaluation device | Compact | Compact |
| Safety Integrity Level (SIL) | SIL 3 | SIL 3 |
| FS60-00 Bracket | ![]() |
| FS60-10 Bracket | ![]() |
| FS65 Cooling air housing | ![]() |
| FH80-00 Bracket | ![]() |
| FH80-10 Bracket | ![]() |
| Flame-Scanner Testing Device FFP30 | ![]() |
| FR20-01 Deflecting mirror | ![]() |
You can find additional accessories in the
product catalogue.
Accessories available via our sales representatives