Tec Center Media Center

TECHNICAL SUPPORT

Headset

+49 (0) 6227 - 6052 - 33

Umschlag

support@lamtec.de

F120I
Flame Monitoring Device

Your advantages at a glance:

  • Suitable for single burners in heating plants and process furnaces
  • SIL3 approval
  • Approved for continuous operation
  • Suitable for fuels such as oil, gas, biomass, dust and process gases
  • Plug-in module for din rail mounting
  • 2 channel system with electronic self-monitoring
  • Designed for mounting in control cabinet
  • Status display via LED
  • No adaptation to country-specific mains frequencies necessary

The new F120I is the result of continuous development of the proven F130I. The F120I impresses with technical features that build on or even surpass the proven design.

Technical Data
 

F120I

Power supply voltage

120V or 230V

Operating mode

Continuous operation

- - - Single electrode operation

Yes

- - - Two-electrode operation

Yes

Ambient temperature

-20 °C … +70 °C

Ionisation assist voltage

390V

Safety time (FFDT)
Reaction time in case of flame failure

1s
3s
5s

Relay output

Flame signal

Open collector output: Flame ON

Yes

Open collector output: Standby

Yes

LED intensity display

Yes

Safety Integrity Level (SIL)

SIL3

Approvals

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 61508, parts 1, 2 and 3
  • DIN EN 50156-1, cl 10.5.5
  • DIN EN 50156-2

EC Type Examination Certificate according to 2016/426/EU (Gas Appliances Regulation)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 61508-1
  • DIN EN 61508-2

SIL 3

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 50156-1, cl 10.5.5
  • DIN EN 50156-2
  • DIN EN 61508, parts 1, 2 and 3

CE Declaration of Conformity

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Module B+D)
  • (EU) 2016/426 (Gas Appliances Regulation GAR)
  • 2011/65/EU (RoHS)
  • 2015/863/EU (RoHS)
 

F130I

F120I

Power supply voltage

120V or 230V

Operating mode

Continuous operation

- - - Single electrode operation

X

Yes

- - - Two-electrode operation

Yes

Yes

Ambient temperature

-20 °C … +60 °C

-20 °C … +70 °C

Ionisation assist voltage

= Power supply voltage

390V

Safety time (FFDT)
Reaction time in case of flame failure

1s
3s

1s
3s
5s

Relay output

Flame signal

Open collector output: Flame ON

X

Yes

Open collector output: Standby

X

Yes

LED intensity display

X

Yes

Safety Integrity Level (SIL)

SIL3

You can find accessories in the
 product catalogue.

Accessories available via our sales representatives

Sales Department

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG