F350 and FFS30
Evaluation Unit F350 and Flame Sensor FFS30

Your advantages at a glance:

  • Configurable with external user interface FB30
  • 3 preselectable operating modes
  • Available as single sensor or dual sensor (UV/IR)
  • Protection class IP66/67
  • Self-learning function flame ON/OFF
  • Operation either via graphical user interface with status display or F300K remote software, mandatory for version without integrated user interface
  • Fail-safe iFSB (internal LAMTEC Failsafe System Bus) between FFS30 and F350
  • SIL 3 according to DIN EN 61508 Part 1-7
  • Flame sensor available for Ex Zone 1

The flame monitoring system FFS30/F350 is mainly used in

  • Complex combustion systems
  • Retrofit
  • Combustion plants with and without selection tasks
  • Single and multi-fuel burners
  • Combustion chamber monitoring
  • Power plants, heating plants, process furnaces, waste incineration plants
  • Combustion plants with restricted view of the flame

Features:

3 in 1: Three flame scanners in one.
Versatile, promising and highly intelligent

The FFS30 flame scanner offers digital flame analysis in both the UV and IR spectral ranges, making it suitable for virtually all combustion applications.

  • Configurable with external user interface FB30
  • Operation with Remote Software
  • Ex zone 1
  • SIL 3

Each model has a semiconductor sensor with two processors that allow continuous operation.
The FFS30 is a compact flame scanner with amplifier and relay units.

The FFS30K UV/IR model has two UV and IR sensors, making it one of the most versatile flame scanners on the market.
It is suitable for demanding applications such as multi-burner installations with different fuels or excessive background radiation.
Three channels allow the application of specific detection parameters for different fuels and operating situations - so the FFS30 combines three flame scanners in one.
Up to 32 FFS30 scanners can be linked and connected to a PC to perform real-time flame analysis and record trends.

Technical Data

F350

FFS30

Approvals

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 61508-2, parts 1, 2 and 3
  • DIN EN 50156-1
  • DIN EN 50156-2

EC Type Examination Certificate according to 2016/426/EU (Gas Appliances Regulation)

  • DIN EN 298
  • DIN EN 13611

SIL 3

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 61508, parts 1, 2 and 3

CE Declaration of Conformity

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 60730-2-5
  • DIN EN 60730-1
  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Module B+D)
  • (EU) 2016/426 (Gas Appliances Regulation GAR)
  • 2011/65/EU (RoHS)
  • 2015/863/EU (RoHS)

USA and Canada

  • UL 60730-2-5, 3rd Ed.

EX certificate FFS30

  • Ex-Zone 1
    • IEC 60079-0
    • IEC 60079-1
    • IEC 60079-11
    • IEC 60079-28
    • IEC 60079-31
    • IEC 60079-7
  • Ex-Zone 2
    • IEC 60079-0
    • IEC 60079-15
    • IEC 60079-31
    • IEC 60079-7
  • Division
    • ANSI/ISA-12.12.01-2015
    • CAN/CSA C22.2 No. 213-15
Non Compact
 FFS07FFS08FFS30
Power supply voltageF152 + 24 VDCF152 + 24 VDCF350 + 24 VDC
Operating modeContinuous operationContinuous operationContinuous operation
Degree of protectionIP66 for Ex zone 1XIP66
IP67 for Ex zone 2No Ex zone only as standard IP67IP67
Sensor typeUV, IRUV, IRUV, IR, UV/IR-1 Dual sensor
UV-1, UV-4, IR-1, IR-1 TUV-1, UV-4, IR-1, IR-1 T, IR-1 T/S2UV-4, UV/IR-1, IR-2, IR-4
Operating temperature-20 °C ... +65 °C (UV)-20 °C ... +65 °C
-40 °C ... +85 °C
Operating temperature-20 °C ... +60 °C (IR)-20 °C ... +60 °C
Ex zone 1II 2G Ex d IIC T6 Gb II 2G Ex d IIC T6 Gb
II 2D Ex tb IIIC T80 °C DbXII 2D Ex tb IIIC T80 °C Db
Ex zone 2II 3G Ex nA IIC T5 (T6)
Ge X
XX
II 3D Ex tc IIIC T95 °C
Dc X
XX
DisplayXXHas to be connected with FB 30
UL resp. Class 1 Div. 2 certifiedUL 372 - UL listedUL 372 - UL listedUL / Cl 1 Div. 2
Operation with Remote SoftwareXXYes
Evaluation deviceF152F152F350
Safety Integrity Level (SIL)F152 SIL 3F152 SIL 3F350 SIL 3
Compact
 F200KF300K
Power supply voltage24 VDC24 VDC
Operating modeContinuous operationContinuous operation
Degree of protection Ex zone 1IP66X
Degree of protection Ex zone 2IP66/67IP66/67
Sensor typeUV, IRUV, IR, UV/IR-1 dual sensor
UV-2, (Ex zone 1, Ex zone 2), UV-6 FO (Ex zone 2), IR-1 (Ex zone 1, Ex zone 2), IR-2 (no Ex zone)UV-4, UV-4.6, UV-4.6 FO, UV/IR-1, IR-4, UV/IR-1 FO (as standard all in Ex zone 2)
Operating temperature Ex zone 2-40 °C ... +75 °C (UV-2, UV-6 FO)
-40 °C ... +85 °C
-40 °C ... +60 °C (IR-1)
Operating temperature Ex zone 1-40 °C ... +65 °C (UV-2)
X
-40 °C ... +60 °C (IR-1)
Ex zone 1Ex II 2G, zone 1 // Ex II 2D- zone 21
X
Ex db lic. T6 ... T5 Gb // Ex tb IIIC T80 °C, T95 °C Db
Ex zone 2Ex II 3G, zone 2 // Ex II 3D zone 22
Ex nA nC ic IIC T5 (T6) Gc X
 Ex nA nC IIC T6 ... T5 Gc X // Ex tc IIIC T85 °C Dc X
UL resp. Class 1 Div. 2 certifiedUL certified/ Cl 1 Div.2UL certified/ UL + Cl 1 Div. 2
Operation with Remote SoftwareXYes
Evaluation deviceCompactCompact
Safety Integrity Level (SIL)SIL 3SIL 3
Flame Scanner Remote Software (FSB) for F350
External User Interface FB30
Connection cable
Brackets with screw connection
Cooling air housing
Power supplies
Junction box
Flame Scanner Testing Device FFP30


You can find additional accessories in the
 product catalogue.

Accessories available via our sales representatives

Sales Department

LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG

to top