Sensors and Systems for combustion technology

Burner Control FA1

Burner Control FA1
  • Control output for mechanical or
    pneumatic compound
  • Connects to PLC systems
  • Simple to program
  • 10-bits resolution
  • Can be operated from PC
  • Integrated load control
  • Integrated leakage test
  • Can be installed directly on the burner

Voltage supply:

from 115 VAC -15 %
to 230 VAC +10 % 50/60 Hz

Ambient temperature
Operation:


+0 °C … +60° C

Ambient temperature
Transport and storage:


-25 °C … +60° C

Resolution per analogue input:

999 digits, 10 Bit

Recommended run time of the positioning drive:

30 s … 60 s; distance max. 10 m; max. current 50 mA

Digital signal inputs

14

BUS coupling:

Via LSB adapter BUS card optional for these systems:

  • Interbus-S (Phoenix)
  • Profibus DP
  • Modbus
  • Ethernet (Modbus TCP)

Zulassungen:

 

 

 

 

 

 

 

EC Type Examination Certificate according to 2014/68/EU (Pressure Equipment Directive)

  • DIN EN 298
  • DIN EN 1643
  • DIN EN 60730-2-5
  • DIN EN 20156-1

 

EC Type Examination Certificate according to 2009/142/EG (Gas Appliance Directive)

  • DIN EN 298
  • DIN EN 13611
  • DIN EN 1643

 

SIL 3 Confirmation

  • DIN EN 61508 Teil 2+3

 

CE Declaration of Conformity

  • 2014/35/EU (Low Voltage Directive)
  • 2014/30/EU (EMC Directive)
  • 2014/68/EU (Pressure Equipment Directive Cat. 4 Mod. B+D)
  • 2009/142/EG (Gas Appliance Directive)


System Acceptance Test - EN 50156-1 (TÜV)

 

Marine Type Approval Certificates GL and LR

 

AGA Certified Product - EN298, AS4625, AS4630

It is possible to adapt the burner control FA1 with the most different combustion tasks. Start with and without pilot burner may be set for oil and gas separately. The integrated leakage check may take place alternatively before ignition or after shut-down.

The display of process status signals and fault status signal take place in plain text in the choosen language. A running time meter is integrated, which counts the burner’s running time both gas and oil. All starts are counted sparately for each operating mode.

By request the Burner Control FA1 adopts the load control of the burner. External setpoint shift (weather control) and start control are included.

  Function

  Communication

  Optional

 

  Start-up counter

 

 

  RS232 interface:
     • Operating
     • Maintaining
     • Remote control
     • Storage

 

 

  Flame monitoring

 

 

  Operating hours counter

 

 

  LAMTEC System Bus (LSB) 

 

 

  Start-up assistant

 

 

  Burner control unit

 

 

  Control instrumentation connection - options:
     • INTERBUS-S
     • Profibus
     • Modbus
     • Ethernet 

 


  Plug kits
     • Inverse terminal
     • Terminal with
        elasticity

 

  Compound regulator

 

 

  Leakage test

 

 

  Burner firing-rate controller